Example for sensor temperature calibration:
o o
reading temperature (77 F) + (-2 F)
If using decimal input If using hexadecimal input
Parameter no. = 13 Parameter no. = 0D
Parameter value = -2 Parameter value = FE ( Size >= 1 byte)
o o
Display temperature = sensor reading value + offset value = 77 - 2 F = 75 F
Reset ZTS-110 to Factory Default Settings
LCD indicationStep Procedure / Description
Press and hold "Fan" + "Mode" keys for
2 seconds to entry the reset mode.
Press Up/Down key to toggle Yes/No
selection.
1
Press "Prog" key once to confirm the action.
=> It will perform the reset if select "Yes" or
=> It will back to home page if select "No".
LCD display done after reset to factory
default settings.
The following data will be reset to default:
1. Clock : 12:00am
2. Day: Mon
3. Temperature scale: F
4. Swing : 2F
5. Diff: 2F
6. Pre-defined schedule
7. Operation mode: OFF
8. Default Heat override set point
9. Default Cool override set point
10.Filter counter cleared
11.Delete from network
12. All configuration parameters value
2
35
Parameter value rangeParameter No.
Functions
o o
-2 (0xFE) = -2 F (-1.0 C)
13 (0x0D)
Sensor temperature
calibration